King air cooled chiller

.

Description

Various protection functions, ensuring safe operation of the system

The system adopts modular structure, and the unit starts up in stages, reducing the impact of the unit startup current on the power grid. The unit is equipped with high/low pressure switch, anti-freezing protection device, flow controller, overload protection device, power phase sequence protection device, and operation control equipment. When a failure occurs, the controller will automatically give an alarm in real time


Module Standby Operation Technology

With the special standby operation technology and the single-module multi-system design, different modules in the same system are standby to each other, ensuring that the system can keep running in an emergency when one or more compressors or modular chillers fail


Micro PC control board, intelligent and real-time adjustment

The micro PC control board features product operation control, safety protection, and many other functions. Among them, the high-speed processing chip can quickly obtain the operating parameters of the host system, and deliver control instructions in time to realize rapid processing, implement smart control of the unit, and ensure the stable operation of the unit

Technical specifications table

Specifications
MC-SS65-RN1
MC-SS130-RN1
MC-SS65-RN1
MC-SS130-RN1
Model
-
65
130
Capacities Cooling capacity
kW
65
130
Capacities Cooling capacity
x 103kcal/h
55.9
111.8
Capacities Heating capacity
kW
71
142
Capacities Heating capacity
x 103kcal/h
61
122.1
Electric parameters Cooling power
kW
19.5
39.2
Electric parameters Cooling current
A
36.4
73.1
Electric parameters Heating power
kW
20.4
40.8
Electric parameters Heating current
A
38.1
76.1
Electric parameters Maximum power consumption
kW
30.1
60.2
Electric parameters Maximum current
A
55
110
Electric parameters Power supply specifications
-
380V 3N ~ 50Hz
380V 3N ~ 50Hz
Compressor Quantity
Pcs
1
2
Refrigerant Type
-
R410A
R410A
Refrigerant Charge amount
kg
11.5
10x2
AC water-side heat exchanger Water flow rate
m3/h
11.2
22.4
AC water-side heat exchanger Resistance loss
kPa
48
60
AC water-side heat exchanger Loading capacity
MPa
1.0
1.0
AC water-side heat exchanger Diameters of water inlet and outlet pipes
mm
DN65
DN65
AC water-side heat exchanger Type
-
Shell and tube
Shell and tube
Air-side heat exchanger Air flow
m3/h
27000
48000
Air-side heat exchanger Number of fans
Pcs
2
2
Air-side heat exchanger Type
-
Fin coil
Fin coil
Dimensions Width
mm
2000
2200
Dimensions Depth
mm
960
1120
Dimensions High
mm
1770
2315
Weight Net weight
kg
525
875
Weight Operating weight
kg
560
938
Operating noise
dB(A)
65
68

Comments ( 0)