Aqua Tempo Power Air-Cooled Chiller Model 60Hz PS

.

Description

Wide application range

Aqua Tempo Power Chillers with cooling capacity ranging from 30kW to 250kW, combination model’s maximum capacity ups

to 2000kW.

Freely combine with fan coil units and air handling units. Project owners may choose the best types according to their design

 

taste (for interior) or functional needs.

Wide ambient temperature and water outlet temperature operation ranges


Advanced technology

High performance heat exchanger

Tube-in-tube & shell-tube heat exchanger

EXV for more precisely flow control


High reliability

Alternative cycle duty operation

Back-up functions

Reliable protections

Intelligent defrosting technology

Technical specifications table

Specifications
MGBT-F30W/DN1
MGBT-F60W/DN1
MGBT-F120W/DN1
MGBT-F180W/DN1
MGBT-F30W/DN1
MGBT-F60W/DN1
MGBT-F120W/DN1
MGBT-F180W/DN1
Power supply
V/Ph/Hz
220/3/60
220/3/60
220/3/60
220/3/60
Cooling1 Capacity
kW
30
60
120
180
Cooling1 Input
kW
10.0
19.5
39.0
58.5
Cooling1 EER
-
3.00
3.08
3.08
3.08
Cooling2 Capacity
kW
26
52
104
156
Cooling2 Input
kW
11.0
22.1
43.0
64.5
Cooling2 EER
-
2.36
2.35
2.42
2.42
Heating3 Capacity
kW
32
65
130
195
Heating3 Input
kW
9.8
20.0
40.0
60.0
Heating3 COP
3.27
3.27
3.25
3.25
3.25
Max. running current
A
45.0
90.0
180.0
270.0
Compressor Type
-
Fixed Scroll
Fixed Scroll
Fixed Scroll
Fixed Scroll
Compressor Quantity
Pieces
2
2
4
6
Air side heat exchanger Type
-
Fin-coil
Fin-coil
Fin-coil
Fin-coil
Air side heat exchanger Fan motor type
-
AC Motor
AC Motor
AC Motor
AC Motor
Air side heat exchanger Qualitity of fan motor
Pieces
1
2
4
6
Air side heat exchanger Air flow
m3/h
12,000
25,000
48,000
72,000
Water side heat exchanger Type
-
Tube-in-tube
Shell-tube
Shell-tube
Shell-tube
Water side heat exchanger Water pressure drop
kPa
60
12
25
30
Water side heat exchanger Volume
L
10
42
64
99.5
Water side heat exchanger Water flow volume
m3/h
5.2
10.3
20.6
31
Refrigerant Type
-
R410A
R410A
R410A
R410A
Refrigerant Charged volume
kg
6
13
26
42
Refrigerant Throttle type
-
EXV
EXV
EXV
EXV
Sound pressurer level4
dB(A)
65
67
70
74
Unit net dimension(D×H×W)
mm
1,514×1,865×841
2,000×1,880×900
2,000×2,080×1,685
2,850×2,110×2,000
Packing dimension(D×H×W)
mm
1,590×2,065×995
2,090×2,055×985
2,080×2,240×1,755
2,980×2,260×2,135
Net/ Gross weight
kg
380/400
580/650
1,180/1,300
1730/2,000
Pipe connections Water inlet/outlet
mm
DN40
DN100
DN65
DN80
Controller
-
Wired controller
Wired controller
Wired controller
Wired controller
Maximum combinations
-
16
16
8
5
Ambient temperature range Cooling
°C
10~52
10~52
10~52
10~52
Ambient temperature range Heating
°C
-10~21
-10~21
-10~21
-10~21
Water outlet temperature range Cooling
°C
5~17
5~17
5~17
5~17
Water outlet temperature range Heating
°C
45~50
45~50
45~50
45~50
Water outlet temperature range5 Cooling
°C
0~17(customized)
0~17(customized)
0~17(customized)
0~17(customized)
Water outlet temperature range5 Heating
°C
22~50(customized)
22~50(customized)
22~50(customized)
22~50(customized)